How to Make Step Down Transformers

Last Updated on January 3, 2025 by Swagatam 162 Comments

A step down transformer is a device which reduces a higher AC potential to a lower AC potential as per its winding ratio and specifications.

Table of Contents
  • Introduction
  • Basic Transformer Design
  • Calculating Primary Winding
    • Winding Data
  • Calculating Secondary Winding
    • Calculating Core size
    • Table Dimension of Transformer Stamping
      • Section 1
      • Section 2
    • Core Assembly Diagram
    • How to Assemble the Transformer
    • How to Apply Shielding
      • For Torroidal Transformer designing, you can refer to the following pdf document:
    • Additional Useful Information Regarding Transformer Winding
    • Simple Calculation of Transformers Up to 2000 Watts
    • Calculation Notes:
    • Power Calculation Example:
    • Core Cross-Section Calculation:
    • Primary Winding Turns Calculation:
    • Primary Current Calculation:
    • Wire Calculation:

In this article we are going to discuss how to design and construct a basic step down transformer which are typically applied in mains-operated power supplies.

Introduction

This will likely help electronic hobbyists to develop and build their very own transformers based on their particular demands.

Within the next pages, a simplified layout method is presented in order to achieve satisfactorily developed transformers. On the other hand, the design process may be a subject of some experimentation.

The tables I have I have explained in this article trim computations short which help the designer to find the appropriate size of wire or even core lamination.

Exclusively pertinent data and calculations are supplied here to ensure that the designer is absolutely not baffled by unwanted details.

Here we will specifically discuss about transformers which possesses 2 or more winding of insulated copper wire around an iron core. These are: one primary winding and one or maybe more secondary winding.

Each winding is electrically isolated from the other however are magnetically connected by using a laminated iron core.

Small transformers possess a shell style structure, i.e. the winding are encircled by the core as demonstrated in Fig. 1.

The power supplied by the secondary is in fact transmitted from the primary, although at a voltage level dependent on the winding ratio of the a pair of winding.

Video Interpretation

transformer parts

Basic Transformer Design

As the initial phase towards the design of a transformer, the primary and secondary voltage evaluations and the secondary ampere rating has to be distinctly expressed.

After that determine the core content to be employed: ordinary steel stamping or cold rolled grain oriented (CRGO) stamping. CRGO features a greater allowable flux density and reduced losses.

The best possible cross-sectional part of the core is roughly assigned by:

Core Area: 1.152 x √(output voltage x output current) sq cm.

With regard to transformers having several secondaries, the sum of the the output volt-amp product of each winding needs to be considered.

The quantity of turns on the primary and secondary winding is determined using the formula for turns per volt ratio as:

Turns per volt = 1/ (4.44  x 10-4 frequency x core area x flux density)

Here, the frequency is usually 50Hz for Indian household mains source. The flux density could be considered as approximately 1.0 Weber/ sq. m. intended for ordinary steel stamping and approximately 1.3 Weber/ sq. m. for CRGO stamping.

Calculating Primary Winding

The current in the primary'winding is presented by the formula:

Primary Current = Sum of o/p Volt and o/p Amp divided by Primary Volts x efficiency

The efficiency of small transformers can deviate between 0.8 to 0.§6. A value of 0.87 works extremely well for regular transformers.

The appropriate wire size needs to be determined for the winding. The wire diameter is dependent upon the current rated for the winding and also the permitted current density of the wire.

The current density could be as tall as 233 amps/ sq. cm. in small transformers and as minimal as 155 amps/ sq. cm. in big ones.

Winding Data

SWGMax. current capacity (Amp)Turns per sq. cm.
1016.608.7
1113.63810.4
1210.96112.1
138.57913.6
146.48721.5
155.25426.8
164.15135.2
173.17845.4
182.53857.3
192.01372.3
201.313106.0
211.0377132.7
220.8183167.4
230.6383210.9
240.5046265.9
250.4004334.9
260.3284415.0
270.2546523.0
280.2024659.0
290.1608830.0
300.1558881
310.1364997
320.11821137
330.10141308
340.08581608
350.07151902
360.05862286
370.04692800
380.03663542
390.02844838
400.02255595
410.01976543
420.01449337
430.011311352
440.009014392
450.007917147
460.005920223
470.004725397
480.003731605
490.002940160
500.001081242

Typically, a value of 200 amps/ sq. cm. may be considered, according to which Table#1 is created. The amount of turns in the primary winding is presented by the formula:

Primary Turns = Turns per Volt x Primary Volts

The room consumed by the winding is determined by the insulation density, technique of winding and the wire diameter.

Table#1 provides the estimated values of the turns per square cm. through which we are able to calculate the window area consumed by the primary winding.

Primary winding Area = Primary turns / Turns per sq. cm from Table#1

Calculating Secondary Winding

Considering that we have the assumed secondary current rating, we are able to determine the wire size for the secondary winding simply by going through Table#1 directly.

The quantity of turns on the secondary is calculated in the identical method when it comes to primary, but around 3% excess turns should be included to reimburse for the internal drop of secondary winding voltage of the transformer, upon loading. Hence,

Secondary turns = 1.03 (turns per volt x secondary volts)

The window area necessary for secondary winding is identified from Table#2 as

Secondary window area = Secondary turns / Turns per sq. cm. (from Table#2 below)

Calculating Core size

The principal qualifying measure in picking the core could be the total window area of winding space accessible.

Total window area = Primary window area + sum of secondary window areas + space for former & insulation.

A little extra space is necessary to support the former and insulation in between winding. The specific quantity of extra area may differ, even though 30% could be considered to begin with although this may need to be customized later on.

Table Dimension of Transformer Stamping

Section 1

Type No.Tongue width (cm.)Window area (sq. cm.)
17 (E-I)1.2701.213
12A (E-I)1.5881.897
74 (E-I)1.7482.213
23 (E-I)1.9052.723
20 (E-I)1.9053.230
15 (E-I)2.2233.230
31 (E-I)2.5883.230
11 (E-I)2.5404.839
35 (E-I)2.5404.839
14 (E-I)2.4615.645
33 (E-I)2.4615.645
11 (E-I)2.5407.259
35 (E-I)2.5407.259
3 (E-I)3.8107.562

Section 2

Type No.Tongue width (cm.)Window area (sq. cm.)
9 (U-T)2.2237.865
9A (U-T)2.2237.865
4A (E-I)3.81010.484
4 (E-I)3.81010.484
16 (E-I)3.81010.891
13 (E-I)2.38115.865
7 (E-I)2.54015.865
6 (E-I)3.81015.865
5 (E-I)3.81019.305
8 (E-I)5.08049.803

The perfect core sizes possessing a more substantial window space are generally determined from Table#2 taking into consideration the gap between lamination while stacking them (the core stacking element may be taken as 0.9), we now have

Gross core area = Core Area / 0.9 sq cm. In general, a square central limb is preferred.

For this, the width of the tongue of lamination is

Tongue width =  √Gross core area (sq.cm)

Now refer to Table#2 once again and as a final point find the appropriate core size, having adequate window area and a nearby value of the tongue width as calculated. Modify thel stack height as needed to acquire the intended core section.

Stack Height = Gross Core Area / Actual Tongue Width

The stack must not be a lot under the tongue width rather should be more. However, it must not be greater than 11/2 times the tongue width.

Core Assembly Diagram

lamination core assembly
Core lamination details

How to Assemble the Transformer

The winding are done over an insulating former or bobbin that fits on the middle pillar of the core lamination.

The primary is generally wound first, and next it is the secondary, keeping an insulation between the two layers of the winding.

One last insulating layer is applied on top of the winding to safeguard all of them from mechanical and vibration deterioration.

Whenever thin wires are employed, their particular ends needs to be soldered to heavier wires in order to bring the terminals outside the former.

The lamination are usually put together on the former by alternate lamination reversed in set up.

The lamination has to be tightly bound together through an appropriate clamping framework or by using nuts and bolts (in case through holes are supplied within the lamination assembly).

How to Apply Shielding

This can be a wise idea to utilize an electrostatic shielding between the primary and secondary winding to circumvent electrical interference from moving across to the secondary from the primary.

The shield for step down transformers can be constructed from a copper foil which can be wound between the two winding for somewhat more than a tum.

Insulation has to be presented across the entire foil and proper care taken in order that the two ends of the foil never come in contact with each other.

Additionally  a wire could be soldered with this shielding field and connected with the ground line of the circuit or with the lamination of the transformer which may be clamped with the ground line of the circuit.

For Torroidal Transformer designing, you can refer to the following pdf document:

https://www.homemade-circuits.com/wp-content/uploads/2021/04/torroidal-transformer_compressed.pdf

Additional Useful Information Regarding Transformer Winding

The following useful data related to transformer winding was kindly shared by Mr. Constantinos Mermygas. I hope the readers will find it very helpful.

copper winding data
transformer calculations

Simple Calculation of Transformers Up to 2000 Watts

Parameters:

  • V = Mains voltage
  • f = Network frequency in cycles per second
  • S = Core cross-section in square centimeters
  • B = Weber per square centimeter (Weber/cm²)
  • 4.44 = Coefficient of constant
  • N1 = Turns of primary winding
  • N2 = Turns of secondary winding
  • I1 = Primary current in Amperes
  • I2 = Secondary current in Amperes
  • W = Transformer power in Watts

Calculation Notes:

  1. Choose Bmax = 1.2 (maximum flux density).
  2. To calculate a transformer, determine the power consumption on the secondary winding and add approximately 10%.

Power Calculation Example:

  • Secondary Voltage: 24 volts
  • Current: 15 Amps
  • Transformer Power: (24 * 15) + 10% = 400 watts

Core Cross-Section Calculation:

  • Example:
    Core cross-section: √400 * 1.2 = 24 cm²
    Central trunk (tongue):
  • Width = 5 cm
  • Height = 4.8 cm
  • Add 5% for varnish, total height ≈ 5 cm

Primary Winding Turns Calculation:

  • Formula:
    N1 = V / (4.44 × B × S × f / 10,000)

Primary Current Calculation:

  • Formula:
    I1 = W / V
    Example:
    I1 = 400W / 220V = 1.818 Amperes

Wire Calculation:

  • Example:
  • Wire Diameter: 1 mm
  • Cross Section: 0.785 mm²
  • Current Strength: Up to 1.960 Amperes

You'll also like:

  • Over Current Cut-off Power Supply Using Arduino
  • wall2Bclcock2Bsupply1.5V Power Supply Circuit Diagram for Wall Clock
  • rfdischargegeneratorcircuitMaking a Strong RF Discharge Circuit
  • 1.25Vto120Vadjustablevariablepowersupllycircuit1.25V to 120V Mains Adjustable Voltage Regulator Circuit Diagram

Filed Under: Power Supply Circuits Tagged With: Down, Step, Transformers

About Swagatam

I am an electronics engineer and doing practical hands-on work from more than 15 years now. Building real circuits, testing them and also making PCB layouts by myself. I really love doing all these things like inventing something new, designing electronics and also helping other people like hobby guys who want to make their own cool circuits at home.

And that is the main reason why I started this website homemade-circuits.com, to share different types of circuit ideas..

If you are having any kind of doubt or question related to circuits then just write down your question in the comment box below, I am like always checking, so I guarantee I will reply you for sure!



Previous Post: « Digital Weighing Scale Using Load Cell and Arduino
Next Post: Capacitor Leakage Tester Circuit – Find Leaky Capacitors Quickly »

Reader Interactions

Questions & Answers

Total Posts: 162 (Older Threads Archive)
Newest Oldest
Faith
February 10, 2018 • 8 years ago #58344

This is a very interesting topic especially for me thank you for that
But what in a case i have a transformer salvage from ups and i want to redesign it how do i go about the calculationt
Thanks and best regards

And as for the sinewave inverter using spwm i’m still on it when I’m done i will share the good news
thank you once more for help God bless you real good

Reply
SwagatamAdmin
February 10, 2018 • 8 years ago #58347

Thank you Faith, for modifying a readymade transformer you may have to go in the reverse manner and first identify the core size and the other parameters then compare them with the values given in the respective tables and subsequently evaluate the wire sizes and the number of turns

Reply
cristian
February 14, 2018 • 8 years ago #58441

hello friend long time

i looking circuit for water level for up tank and down tank
down tank is whit water and up is low level turn pump on and so

and what y think i use a automotive rele 30amp to turn a 3hp 220 water pump ?

Reply
SwagatamAdmin
February 14, 2018 • 8 years ago #58446

hello cristian, you can use any set-reset circuit using IC or transistor, and use the “set” points at the bottom of the ground tank and use the “reset” points at the brim of the overhead tank, and wire the relay accordingly.

yes 220V/30 amp relay will work

Reply
cristian
February 14, 2018 • 8 years ago #58454

i show this but not look ic model

tablero con automatico para tanque cisterna listo para usar D NQ NP 675905 MLA25094466995 102016 F

Reply
SwagatamAdmin
February 15, 2018 • 8 years ago #58466

the design is correct, may be the ICs are IC 555

Reply
charan
February 17, 2018 • 8 years ago #58533

This was useful.Hope you can make a similar post on ferrite core transformers and its switching supply circuits.

Reply
SwagatamAdmin
February 18, 2018 • 8 years ago #58544

I am glad you liked it, if I happen to find the ferrite core formulas, will surely update it here…

Reply
Sherwin Baptista
March 1, 2018 • 8 years ago #58838

Dear,
Now I’ve started to build my own transformers (i’m describing an IRON CORE trafo). First i considered this difficult and never knew how to do so. Previously i had to compensate someone in the field to build as per my specs.
Now I’ve cracked the way how to build my own only after seeing this page in your blog.

I’ve got the stamping and frame ordered from Lamington road, purchased varnish and other basic materials required to build the transformer.
Till date I’ve made just one successfully.

I calculated all the electrical parameters involved in its construction and now its been constructed and working properly.

Reply
SwagatamAdmin
March 1, 2018 • 8 years ago #58842

That’s great Sherwin, I am glad you could do it so easily…keep up the good work

Reply
paaker
September 3, 2018 • 8 years ago #62807

Hi Swag,

I got some microwave oven transformers. to rewind for battery charging / inverter purpose. I try to rewind this transformers secondary line 12-0- 12 my coil gauge was SWG 10 and I have rewinding it bifilar type finally I got
8v-08v coz no more space to wind.and its working perfect. on this way I have rewind several transformers with different gauge wires.

now my question is I know how much the voltage output from this transformer. but how to check how much ampere its giving. it is possible to check a transformers output current without connecting a load?

regards.

Reply
SwagatamAdmin
September 4, 2018 • 8 years ago #62809

Hi Paaker, probably the only way to know is by connecting a correctly rated ammeter directly across the output wires of the transformer and check the measurement. Do it only for a couple of seconds, otherwise the transformer or the meter or both could start fuming.

Reply
paaker
September 6, 2018 • 8 years ago #62854

fine.
its possible to make a Battery charger with this transformer( 8v-0v-8v) to charge 12V 150A battery? I thing my transformer is around 40-45A. coz the wire I use to wind it was SWG 10.

Reply
SwagatamAdmin
September 7, 2018 • 8 years ago #62857

yes its possible. use the outer wire to get 16V, and then add a voltage regulator to stabilize at 14.2V

Reply
Paaker
September 7, 2018 • 8 years ago #62864

Fine,
can you please suggest me a perfect circuit for this purpose.

Regards.

Reply
SwagatamAdmin
September 7, 2018 • 8 years ago #62869

Here’s a simplest design:
DC motor mosfet speed manage

Replace the motor with a 1K resistor, adjust the pot to get exactly 14.2V across the 1K

That’s all…now you can connect your battery and let it charge until its terminals reach 14.2V.

For better protection connect a 0.3 ohm 25 watt resistor in series with the positive line, put this resistor over a large heatsink, and do the same to the mosfet also

Reply
Osei Kwame
May 30, 2019 • 7 years ago #67339

teacher Swagatam I was reading your article on transformer calculations
now how do I know out put current when calculating core area per your calculations. 2 is this formula applicable to E and I transformers that handle 5Kw of power thanks teacher

Reply
SwagatamAdmin
May 31, 2019 • 7 years ago #67341

Hello Osei, The formulas are applicable for 5 kW but the tables are not, they are limited to 10 amps max.

Reply
Osei Kwame
June 1, 2019 • 7 years ago #67347

Thanks teacher Swagatam

Reply
DEV DATT
June 4, 2019 • 7 years ago #67453

Sir thanks for such a good circuit diagrams & details the one thing which is very important designing the transformer for SMPS Power supplies so sir is it possible to have some help from your side related to this topic as this is a very critical.
Hope to receive the reply.
Thanks & Regards

Reply
SwagatamAdmin
June 4, 2019 • 7 years ago #67454

Thank you Dev, you can read the following post:

https://www.homemade-circuits.com/how-to-design-and-calculate-ferrite-core-transformers-for-inverters/

Reply
Victory
June 22, 2019 • 7 years ago #67861

Good day sir, is it possible to wind like 10pcs of wire at same time for primary coil to make it faster and fewer number of turns and join end to start

Reply
SwagatamAdmin
June 23, 2019 • 7 years ago #67867

Victory, the number of turns should be as per the calculations, adding more number of wires will increase the current handling capacity of the winding.

Reply
Christo
June 23, 2019 • 7 years ago #67877

Hi Swag,

As they say the truth, in simple English, shall set you free. Thank you. This is the first clear discussion I see on trafo’s, especially the relationship between changed voltages and currents. I was particularly concerned about the effect of the changes in current in step-down trafo’s. One thing that became very clear is that I can imagine any situation and start from there. I can then practice the formula’s in every way possible to understand all the effects of all the different designs. This also gives me the ability to reverse engineer existing trafo’s and understand things even better.

Thank you, I like the way you explain things that I can follow your thinking. That makes it every easy to turn my own thinking onto something real.

Reply
SwagatamAdmin
June 24, 2019 • 7 years ago #67882

Thanks Christo,
I am glad you found it useful…please keep up the good work!

Reply
Tolu
June 26, 2019 • 7 years ago #67932

I made a 78va capacity trafo inverter, i load it With 110w appliances, what may bẹ the effect technically.

Reply
SwagatamAdmin
June 26, 2019 • 7 years ago #67937

Output voltage will drop proportionately

Reply
Tolu
June 26, 2019 • 7 years ago #67933

I saw a 1.5kva/24v inverter, the trafo guage amperage was 21.2amps for the battery side and the ac output sise was 2.64amps. please explain how it is so. For this inverter, it is suppose to be 55amps for the battery side which is not feasible

Reply
SwagatamAdmin
June 26, 2019 • 7 years ago #67938

Pleas multiply the primary side voltage with its current, and the secondary side voltage with its current to get the wattages at the relevant sides of the trafo.

Reply
Sam
July 24, 2019 • 7 years ago #68725

Hi swagtam. I used the turn per voltage formula and fixed these values: 1/(4.44*10^-4*50hz*528mm^2*1.1) giving me a total of 1/12.89376, equals 0.077556895turns per voltage, please help me calculate it using my values. The 528mm^2 is the core area, and i got it from tongue width: 1.6cm * tongue depth: 3.3cm. Please help me out

Reply
SwagatamAdmin
July 24, 2019 • 7 years ago #68729

Hi Sam, we have solve it from top towards bottom, meaning start with current and the voltage of the primary and secondary and so on, it can be very difficult to do the opposite way.

Reply
Sam
July 24, 2019 • 7 years ago #68731

Please swagtam what unit is there after the 1.152 in the core area formula, help me write it out in english, my phone displayed the unit as a tiny box (my phone cannot read the unit). Thanks for the previous reply.

Reply
SwagatamAdmin
July 24, 2019 • 7 years ago #68736

Sam, That’s a square root symbol.

Reply
Sam
July 25, 2019 • 7 years ago #68740

Thanks, and also swagtam i have an e core measuring 1.6cm tongue width and 3.3 tongue depth, i use the turn per volt formula and i get 8.53turns per volt but i think its wrong. Please help me calculate the turn per volt using my details, the frequency is 50hz, i just want to know if my answer is right. Please help me calculate it.

Reply
SwagatamAdmin
July 25, 2019 • 7 years ago #68747

Hi Sam, This article is about iron-core step down transformer, it’s not for ecore.

Reply
Ceaser Molobye
September 27, 2019 • 7 years ago #70541

Good day sir
What is the acceptable gap between the lamination of a transformer unit of a 630kva oil cooled minisub and the bottom of the tank, the voltage is 6600/550v

Reply
SwagatamAdmin
September 27, 2019 • 7 years ago #70545

Good day Ceaser, sorry I have no idea about it…

Reply
Shashi Kiran
October 3, 2019 • 7 years ago #70702

What type of a transformer is used in a mosquito bat ? its a small black with yellow jacket around it.

Reply
SwagatamAdmin
October 3, 2019 • 7 years ago #70707

It is a calculated ferrite core transformer. The calculation formulas are explained in this article:

https://www.homemade-circuits.com/how-to-design-and-calculate-ferrite-core-transformers-for-inverters/

Reply
Jan
February 20, 2020 • 6 years ago #76811

Hi Swagatam,
I intend to build my own transformer winding Machine. I find it difficult to find plans to do this even on youtube. Could you perhaps suggest where I can get the necessary info.
Your assistance will be much appreciated.
Regards
Jan

Reply
SwagatamAdmin
February 21, 2020 • 6 years ago #76814

Sorry Jan, presently I do not have any information regarding transformer winding machine. If I happen to find it I’ll surely update in my blog.

Reply
Jan
February 21, 2020 • 6 years ago #76817

Thank you Swagatam

Reply
Ralph Koeniger
April 5, 2020 • 6 years ago #77689

Hello Swag,
Sincerely appreciate gentlemen like you who help tinkerers like us! I just bought a kiln requiring 208volts and my service is 242volts. The kiln manufacturer tells me I can run the kiln, but the elements will fail prematurely, replacement cost for 240 elements is $700+. Would you be so kind as to help me create a drop down transformer either for each leg of 17 or so volts or in combo of about 32 volts, please? I can make the steel core parts and wind the whole thing by hand – I am very meticulous. Have more time than money! Hahahaha!!!! I am not the best at math so doing the calcs myself without guidance from a seasoned vet like you, would not be smart on my part. I don’t want to blow up the kiln I just invested $500 in. Thank you very much – in advance!

Reply
SwagatamAdmin
April 5, 2020 • 6 years ago #77692

Thank you Ralph, A transformer based design may not be so appropriate since it will be bulky, difficult to calculate and prone to mistakes. The easiest and the ideal way to provide a controlled power to a kiln element or any resistive load is through a triac based phase chopper circuit as explained in the following article:

https://www.homemade-circuits.com/how-to-make-simplest-triac-flasher/

You can use any of the the last two designs for controlling your kiln element heat very efficiently and provide a long life to the element.

Reply
Ralph Koeniger
April 5, 2020 • 6 years ago #77710

Hey Swag,
Greatly appreciate the speedy reply. I reviewed your recommendation and think the second design would be best with just a couple increments (resistors) rather than 4, but I have some concerns of which may or may not be warranted based on my limited knowledge on the subject… namely – “minimum transients and spikes” & “generation of lots of RF.” The kiln draws 53 amps and has a digital controller that ramps up temp, holding times, etc. Will there be varied voltages, RF emissions that interfere with the controller and are the components capable of handling 53 amps? Thank you!

Reply
SwagatamAdmin
April 6, 2020 • 6 years ago #77717

Thanks Ralph, there will be RF emission when the load is operated with reduced power, and the Rf will decrease as the power on the load is increased using the potentiometer. However the L1, C1 is specifically to cancel these RF, so if these are correctly optimized, the RF emission can be expected to be minimum. The L1, C1 will also work to absorb spikes and transients.

53 amps looks very high, so the triac will need to be rated accordingly. Finding a 60 to 100 amp triacs is not easy, so this may be an issue.

To solve this a simpler design could be as shown below:

mosfet pwm kiln temperature controller circuit

This design might also work as efficiently as one can expect. The bridge rectifier will also need to be rated at 60 to 100 amps

Reply
Ralph Koeniger
April 15, 2020 • 6 years ago #77921

Hello again Swag, I contacted an electronic parts supply company, emailed the schematic you recommended and they replied:
“In order for us to locate a components on our website, please provide specification for each component on the diagram.”
So I called the tech support department and they said they need more information on the individual parts, their values, voltages, style of the caps, etc. I know I am asking a lot, but could I impose upon you for some detail on those components so the supply house can find them for me, please? Thank you.

Reply
SwagatamAdmin
April 16, 2020 • 6 years ago #77929

Hello Ralph, In general when the part numbers are without specifications that suggests any variant and type can be used.
In this circuit, resistors can be 1/4 watt 5%, pot can be any 5K or 10K linear pot, capacitors can be ceramic disc type, MOSFETs can be IRF740 10nos in parallel.

Bridge rectifier should be 70 to 100 amp rated, IC can be any IC 555

Reply
Ralph Koeinger
April 16, 2020 • 6 years ago #77939

Thank you so very much, really appreciate you going back and forth with on this. You are very kind!

Reply
SwagatamAdmin
April 16, 2020 • 6 years ago #77941

It’s my pleasure, thanks!

Reply
Ralph Koeniger
April 22, 2020 • 6 years ago #78081

Good afternoon Swag,
Hope you and yours are well.
Got all the components, but the 470R (its on the way). Unfortunately I am a bit confused as to how to actually make the connections. I am especially confused about how (which terminals) the two 120v legs from the panel connect to the Rectifier and then how the dropped voltage (104v) legs go back to the Kiln. The mosfet has three legs, it connects to the 470R – how? The G leg appears to be an output going to the load, but the load has two 104v legs required to run it? The 1K resistor connects to 4, 8 & +12volt AND pin 7 from the 555 IC? What about the negative12v leg – where does it connect? How does the 5K connect to the 1N4148, and pins 6 & 2, but how? I laid out the parts, lined them up and labeled them, took a picture of it, but don’t know how to attach it. Sorry about being such a neophyte, can’t get this wrong. BTW I have a couple pretty big heat sinks with fans to cool the rectifier and mosfet. And I’m using a computer 12v pwr supply. Thank you!!!

Reply
SwagatamAdmin
April 23, 2020 • 6 years ago #78101

Hi Ralph,

the connections has to be exactly as shown in my previous diagram. (+) of the bridge goes to the load, the other leg of the load goes to the MOSFET drain. The bridge (-) and the 12V (-) must join as a common negative line, which is indicated as the 0V line in the diagram. So the -12V or the negative of the 12V must connect with the indicated 0V line of the circuit.

Reply
SwagatamAdmin
April 23, 2020 • 6 years ago #78102

the pot center pin goes to pin6/2 o the IC, and the other outer pins go to the diodes.

Reply
Ralph Koeniger
April 23, 2020 • 6 years ago #78104

Thank you Sir! I’m on it!

Reply
Ralph Koeniger
April 25, 2020 • 6 years ago #78137

Hello yet again Swag,
You have been gracious with your time and information. I feel like I need to pay you for this and will if you wish… On the other hand, if I have “overstayed my welcome” on this forum, please simply don’t respond, I completely understand. Otherwise, I have just a couple final questions…

1. The S leg on the mosfet goes to 0V? What about B, the back of the mosfet, does that need to go to ground or should it be isolated? I will be mounting it to its own heatsink.
2. Does the pot dictate the voltage coming out of leg 3 of the IC, therefore determining the voltage coming out D leg of the Mosfet? Is there a tolerance for the pot?
3. Will the voltage going to the load, (one leg coming from D, on a 6AWG, and the other coming from the + side of the bridge also 6AWG), will each leg going to the load be around 104volts AC? The bridge will be mounted to a fan cooled heatsink, should the back be grounded or isolated?
4. Speaking from my VERY limited knowledge and pardon me for even questioning – but I don’t understand connecting the neg of the 12v pwr supply to the ground (0V) from the electrical panel. Could it just connect to the 100n at leg 5 of the IC or does it need the loop kinda thing? It must frustrate you dealing with neophytes like me. Sorry for troubling you with these questions, but thank you for helping.

Reply
SwagatamAdmin
April 25, 2020 • 6 years ago #78154

Hello Ralph, I’ll try to answer your questions:

1) The back of the MOSFET can remain isolated from the supply lines. Only a heatsink may be clamped with the MOSFET back.
2) The pot adjusts the pulse widths of the pin 3 output pulses.
3) THe bridge output will be 104 AC x 1.41 = 146.64 V DC. The back of the bridge can also remain isolated if it has 4 individual legs on the other side.
4) You can connect the negative of 12V to any point of the shown 0V line.

Reply
SwagatamAdmin
April 17, 2020 • 6 years ago #77975

Hello Devendra, i have a PCB related article posted in my website, you can find it here

https://www.homemade-circuits.com/how-to-make-pcb-at-home/

Reply
DHARNIDHAR KUMAR
May 28, 2020 • 6 years ago #79057

sir apka table no 1 16 ampear tak he ha 40 ampear ka liya kya kar kon swg wire and turn per square meter use kara

Reply
SwagatamAdmin
May 28, 2020 • 6 years ago #79062

Dharnidhar, the range of the above calculation is 10 amp maximum only, 40 amp cannot be made using the above calculations

Reply
DHARNIDHAR KUMAR
May 29, 2020 • 6 years ago #79086

DEAR SIR TO HAM 18V-0-18V,40A PRIMARY TO 0-230V-600V AND 12V AC SECONDRY TRANSFORMER KAISE BANAEN

Reply
SwagatamAdmin
May 29, 2020 • 6 years ago #79087

Sorry mere pass uska data nahi hai abhi. Ebay se readymade sample kharid kar check kar sakte ho.

Reply
DHARNIDHAR KUMAR
May 29, 2020 • 6 years ago #79092

DEAR SIR AAPKE PASS KOI FORMULA HAI JISSE KISI BHI TRANSFORMER KA DATA NIKALA JA SAKTA HAI

Reply
SwagatamAdmin
May 29, 2020 • 6 years ago #79096

You can try this article for the basic formulas!

https://www.homemade-circuits.com/how-transformers-work/

Reply
Ulises Aguilar
June 10, 2020 • 6 years ago #79338

hellow my friend , hope family doing well and taking care , I´m looking for good Zerner tester , to check the Volt if it could test up to 554 volt

Reply
SwagatamAdmin
June 10, 2020 • 6 years ago #79355

thanks friend, I am good, presently I do not have the mentioned circuit, if possible I’ll try to update it in the coming days.

Reply
Skywatcher
July 18, 2020 • 6 years ago #80517

Very useful ideology

Reply
Satish Vemuri
July 24, 2020 • 6 years ago #80698

Sir,

Hope you’re doing well … !!!

In recent times i have reviewed couple of Youtube videos on HD Step Down Transformers Home Made, in most of the videos people show calculations in Inch. Where as in your article, shows in cm. When compared, process is similar, however formulas are different.

Finally when get SWG values from datasheet, in your article data sheet of SWG based on amp and Turns per Sq Cm, where as others mention, SWG based on Diameter of Inch, MM, MM2, kg/m

Concern is SWG and its values are different. So which one would you suggest to prefer. In most of the videos first we should find out Bobbin size and stack size of EI Core.

In your article, its all based on total power (Watts) and when we find out total winding area subjected to Primary and Secondary, we will find out from table and can know what would be EI core type for power.

So please tell, how come SWG values are differ.

Reply
SwagatamAdmin
July 25, 2020 • 6 years ago #80706

Satish, it doesn’t matter how the units are calculated or which approach is used for designing the transformer, ultimately the number of turns and the thickness of the wire will be approximately the same for all the standard methods of calculations. The transformer dimension solely depends on the wattage, voltage and current of the transformer.

Reply
Abdul Latif
October 13, 2020 • 6 years ago #83426

Hello Swagatam,
Thank this useful article. I have a small 110/220 volt transformer that I used as a step down transformer when I travel to a 220v country. I burnt this transformer one year ago by putting the 110v side into 220volts source. Now, after reading your article, I decided to rebuild the transformer using your knowledge. But I have a question, the transformer tag says it is 100 watts, core area is 2×2.5 cm. I used the formula Core Area: 1.152 x √P and found the manufacturer’s 100 watts is not correct.

Reply
SwagatamAdmin
October 13, 2020 • 6 years ago #83436

Hello Abdul, yes the manufacturer normally do not provide the correct wattage, they always tend to put higher than the real values…

Reply
Lambhuc
December 7, 2020 • 6 years ago #85095

Is there any other simple way to design isolation transformer?

Reply
Godfrey Godfrey
December 14, 2020 • 6 years ago #85330

Dear sir, please sir, by means of measurement using a meter rule:

1. Is the Core Area = Tongue width x the short length of the center limb(i.e stack height) Or is the Core Area = Tongue width x the long length of the center limb?
2. Is the I – irons coupled with the E for determining the four measurements (i.e stack height, tongue width, window area and core area) Or is the four measurements determined only from the E – irons assembly?

Reply
SwagatamAdmin
December 14, 2020 • 6 years ago #85349

The details are given in the following diagram, the parameters are exactly as shown in the image:

core assembly

Reply
Godfrey Godfrey
December 15, 2020 • 6 years ago #85375

Yes sir, I saw the Core Assembly diagram already.
But I was unable to figure out which and which length of the center limb of the core makes up the Core Area, since you have not indicated using arrows like that of stack height, tongue width and window area.

So please sir, clarify this for me please:
Is the Core Area = tongue width x the long length of the center limb?
Or is it
Tongue width x the short length of the center limb (which can be imaged as stack height)?

Please sir, the reason I ask the question is that I have a stabilizer(automatic voltage regulator) transformer I want to disassemble and make new windings on it to become inverter transformer.

Please sir, the other thing I asked you was :
If the I – irons is included in the Core Assembly diagram for the four measurements (i.e core area, stack height, window area and tongue width)
Or it is only E – irons?
Please sir, clarify this for me. Thank you very much.

Reply
SwagatamAdmin
December 15, 2020 • 6 years ago #85379

Godfrey, the core area = tongue width x stack height, or simply the L x B of the central pillar of the E-core.

The dimensions of the I iron laminations will be exactly as per the E-core lamination and cross section, as shown below:

iron E and I core lamination dimesions and set up

Reply
M.
December 15, 2020 • 6 years ago #85362

Hi every1!
I’m looking for thoose sheets to build a transformer,
-where can i order such?
…without “minimum order: 1 ton / 2000 lbs.”
Thanks!

Reply
Godfrey Godfrey
December 16, 2020 • 6 years ago #85389

Okay sir, thank you very much sir.
Please sir, in other words, can the L x B of the bobbin be taken as core area?

Again, Please sir, am still confused of this point:
For an inverter with 230/12-0-12V, 10A transformer
Is the inverter power rating = 12 x 10 = 120VA or 24 x 10 = 240VA?

Thank you very much sir for your time.

Reply
SwagatamAdmin
December 16, 2020 • 6 years ago #85397

Hello Godfrey, the transformer current rating provides the information regarding the output current of the unit, which is usually the stepped-down voltage side, so for your example it will be 12 x 10 = 120 watts.

Reply
Charles Bonnnici
January 15, 2021 • 6 years ago #86146

One of the best websites for DIY transformer. I really thank you. People like you make a big difference.

Reply
SwagatamAdmin
January 16, 2021 • 6 years ago #86156

Thank you very much, glad the post helped you!

Reply
Charles Bonnici
February 8, 2021 • 5 years ago #86830

Very informative and to the point. Well done God bless you though you are already blessed. You make a difference.

Reply
SwagatamAdmin
February 8, 2021 • 5 years ago #86840

Thank you for kind feedback!

Reply
Don Fring
March 31, 2021 • 5 years ago #88139

I have been looking for a way to create a 12VDC to 6VAC 2A output via a full isolation (voltage only – RFI passing is OK) transformer for over 10 years now and some may have have seen my requests in various circuit online offerings for going on this long. No takers yet. Seems simple but must be a catch. There are not even any low-voltage DC to AC buck converter devices I can find on eBay, Ali, etc. so it must be that I have to make my own. (Seems a crime to use an inefficient and loss-full 12VDC to 120AC inverter to power a wall adapter that outputs 6VAC with 2A maximum output, particularly when solar and 12VDC is my only available power source, and with only 400W of solar providing all individual daily electrical needs.) And while the 12VDC to 120VAC to 120VAC to 6VAC conversion with commercially available equipment has significantly more phantom load when not charging than the 2mA one would assume using a conventional DC to DC buck converter for some DC need. The level of help I am looking for e.g. if there are no commercial transformers for this project, I could wind one, what is the shell of transformer I should order and how many wraps of what gauge wire. Also what is a good 555 and couple of MosFETs perhaps in a push pull at around 60Hz that seem to be a good solution? I think this project is sort of a “contrary to everything” need because most power transfers demand much more efficient use of toroid coils and high speed switching circuits and this one is a poky 60hz. There are many other factors where devices working at such speeds and voltages just aren’t needed that much these days and are thus of no day to day popular interest.

Reply
Arthur Francis Zacchia
August 20, 2021 • 5 years ago #95025

I have a transformer thats 12-0-12 I wound it so no voltage is produced at the 2 wires there is no 24 volt. Is that correct.

Reply
SwagatamAdmin
August 20, 2021 • 5 years ago #95065

If you have applied the mains AC at the primary, and you are not getting any voltage at the secondary, then it is wrong

Reply
Arthur Zacchia
August 20, 2021 • 5 years ago #95081

I tried to go in to more detail I am not building a step down, this is a inverter transformer. I got all done and it said I asked the same question. Thanks for your time.

Reply
Arthur Zacchia
August 20, 2021 • 5 years ago #95080

Thank you for your time, I guess I should have stated I am working on a inverter transformer. The first time I wound it I started with two wires as the center tap. Then wound both wires together in the same direction. Now I have two ends and a center tap. I got 12 volts from one wire using the center tap then got 12 volts from the other lead and center tap. When I measured the two end and not the center tap I should have 24 volts. The no reading 0 volts. That what I saw and was told to do for a interverter transformer. Now I tried the other way doing one wire at a time and putting insulation between the two wires. Now I have 24 volts on the two leads and 12 volts one each side of the center tap. Which one is correct ? Of the two ways of winding. Thanks

Reply
SwagatamAdmin
August 20, 2021 • 5 years ago #95085

24 V voltage across outer leads, and 12 V between the outer and the center tap is the correct result, and the correct winding.

Reply
Timileyin
August 31, 2021 • 5 years ago #95972

Step down 220v to 12v
(1) Give turns per voltage 220v
(2)give turns per voltage 12v
when my stack is 12cm and my tongue 5cm

Reply
Leonardo Togneri
September 13, 2021 • 5 years ago #97219

I am moving to Europe and I have several electric tool that I would like to use there.
The strongest tools are a miter saw and a worm drive circular saw, both using 13 amps at 110 volts, single fase, 60 herts. Italy has 220 volts, 55 herts electricity.
Is it possible to build a transformer to run a circuit sufficient to to use my tools?

Reply
SwagatamAdmin
September 13, 2021 • 5 years ago #97231

Yes that’s definitely possible. The easiest way probably is to buy a 220 x 7 = 1540 watt transformer, check the resistance of the 220 V side, then remove the secondary side winding and replace it with a winding that’s identical to the 220V side, but with 50% less resistance than the 220V side. The thickness of the wire must two times more than that of the 220V side wire.

Reply
mohammad reza mokhari
October 15, 2021 • 5 years ago #101412

dear sir
I calculate low scale transformer as follow But in the this calculate don’t know amounts “K” & delta
1)- S=k * square (p) S is area & p is apparent power in terms of v.a For 100 to 500 watt transformers
2)- d=1.13 * (square(I/delta)) d is wire Diameter & I is current
Yours sincerely

Reply
SwagatamAdmin
October 15, 2021 • 5 years ago #101472

Hello Mohammad, sorry I do not have any information about the formula suggested by you, so can’t help you with this.

Reply
Spyros T
November 14, 2021 • 5 years ago #104776

Hello, first thanks very much for sharing your work, it is truly usefull, is there some book or paper i can find more about this subject?

Reply
SwagatamAdmin
November 15, 2021 • 5 years ago #104799

You are welcome!, if you search online you may find many relevant information.

From this website you can also refer to the following article:

https://www.homemade-circuits.com/how-transformers-work/

Reply
Eniola
November 16, 2021 • 5 years ago #104879

Hi sir, can the above core area, turns per volt formula work extremely well will an ordinary iron core also?or just for crgo only?

Reply
SwagatamAdmin
November 16, 2021 • 5 years ago #104882

Yes it can

Reply
Vishwa Mukh Bharadwaj
March 20, 2022 • 4 years ago #116673

Sir,
Good evening,
I have salvaged a transformer from an UPS. The wires from the transformer connected to the 12V battery are thicker(E72332 AWM 1015 12AWG 600V ,yellow and black.) Normally it is a step down transformer to charge 12V battery. In case of power failure it acts as a step up transformer to power the computer. The wires are thinner (LL34978 18AWG 600V , red and white). Why?
It further says core is not earthed, risk of shock. What does it mean?
Thanks for your help.

Reply
SwagatamAdmin
March 21, 2022 • 4 years ago #116721

Vishwa, the side of the transformer which is rated at low voltage will always have thicker wires since it carries higher current, and oppositely the side which is rated at higher voltage will carry lower current and therefore will have thinner wires.

If you are using a 3 pin plug for the 220V mains side, then the earth pin should be usually connected to the core of the transformer to avoid any kind of shock.

Reply
Vishwa Mukh Bharadwaj
March 21, 2022 • 4 years ago #116729

Sir,
Good afternoon,
Got it. Thanks a lot for your prompt reply.
Regards,
Vishwa Mukh Bharadwaj

Reply
SwagatamAdmin
March 21, 2022 • 4 years ago #116735

You are welcome Vishwa!

Reply
gsrao
September 15, 2022 • 4 years ago #133254

sir,i have doubt .how to find exactly core window area. any formula is there,let me know sir.

Reply
SwagatamAdmin
September 15, 2022 • 4 years ago #133255

Hi GSrao, the method of finding window area is explained in the article. It is to be identified from the table#2. There’s no formula for this.

Reply
João Sousa
November 3, 2022 • 4 years ago #134317

Hello Swagatam,

Can you explain the meaning of the designation 1.5VA in a 230/9V AC transformer.
I read all the articles about transformers you wrote and didn’t find this explanation (sorry if I didn’t).

Best wishes

Reply
SwagatamAdmin
November 3, 2022 • 4 years ago #134330

Hello Joao,
The 1.5VA indicates the maximum average power the transformer would be able to deliver to the load. This value could be also used to find the average current capacity of the primary and the secondary winding of the transformer. You can simply divide the 1.5 with the primary/secondary voltages to get the current ratings of the respective winding.

Reply
João Sousa
November 4, 2022 • 4 years ago #134358

Hello Swagatam, thank you for your reply.

Best wishes,

Reply
SwagatamAdmin
November 4, 2022 • 4 years ago #134366

You are welcome Joao!

Reply
Constantinos
November 17, 2022 • 4 years ago #135042

Swagatam Allow me
Hello João Sousa. I will tell you the same as Swagatam, but in different words.
What I’m going to tell you is in a general context, because I don’t want to confuse you with complex calculations.
The VA is exclusively a unit of measurement of electrical power, and is obtained by multiplying the voltage by the current. 1 Volt × 1 Ampere = 1VA, or 6 Volts × 1.5 Ampere = 9VA.
In your case, VA is the same as watts. The difference between VA and Watt is that with Watt we measure active power, while with VA we measure both reactive power and apparent power.
Also, with Watt we also measure mechanical Power, while with VA we measure only electrical power.
In your case, if you divide 1.5VA by the voltage you will find the current of the secondary (1.5 ÷ 9 = 0.166666667 Αmperes). You can do the same with the primary winding.
Note: I used a translator. I don’t know the English language

Reply
João Sousa
November 18, 2022 • 4 years ago #135226

Hello Swagatam and Constantinos, thank you for both replies.

I looked for more information on the subject, and found these two formulas:
I=U/R(A) and P=UxI(W)
And now I know that both can be related (in case the circuit is pure resistive, if it is for motors we also have to consider the value of cos(fi)), but when I read the article about the calculation of transformer windings, I didn’t find any reference to “VA”s , and I thought, after all, what are we calculating in practice? and how does it relate to the characteristics of prefabricated transformers that are on the market today?.
And to add to my doubt, I have an old transformer (Still working in a sewing machine, with the characteristics 220V;110V/12A).
In summary, at some point in time the value in Amperes was no longer used, to be replaced by VoltAmpere to designate the maximum operating value of a transformer for a given voltage value (in the “modern” designation it would roughly be, 110X12= 1320VA)

Best regards

Reply
Constantinos
November 19, 2022 • 4 years ago #135315

I’ll start with the 220/110 Ω-12A transformer……If the transformer has a secondary voltage of 110V and 12A, then you’ve calculated correctly 1320VA .
I’ll try again, in other words. VA is the apparent power, i.e. what we see. Probably what the gauges see. But what we see is not always correct. While the watt is the real power, when we connect the load (the consumption).
When we calculate a transformer, we calculate it in watts, regardless of whether we connect a resistive consumer, or whether we connect an inductive one.
Also, VA is the operation of a multiplication. It might be 10 volts by 2 amps, but it might be 2 volts by 10 amps. the result in both cases is the same (20VA)
I have no intention to offend you, but these concepts are for people who have a lot of experience and advanced knowledge. Even electricians have a hard time understanding these concepts.
The transformer when it is above 2500 watts, is not something simple to calculate. But when he is smaller, the watts and the VA have little difference., and it is not worth bothering so much. Actually, I don’t do such detailed calculations either, and that’s my job.
But don’t confuse amperes with VA. Volts are the force that makes electrons move. While amperes are how many electrons move in a second second. But this is not going to help you at all. On the contrary, it will confuse you more.
These topics are discussed by mechanical-electrical , and radio-electrical engineers.
You, keep in mind that the VA is the same as the watt.
However, if you have any other questions, I’ll try to explain them to you.
My best wishes from Greece

Reply
João Sousa
November 19, 2022 • 4 years ago #135366

Hello Swagatam, and Constantinos thank you for your reply.

I didn’t feel offended at all. I only referred to a concrete example, of an old transformer that refers to the value in Amperes and not in “VA”s. I’m looking for components to build a power supply, and at the store they asked me how many “VA”s will I need in the transformer? And I couldn’t say… I answered 4, 5A at the most! In the store they weren’t able to suggest any or explain what the value in “VA” means and why it’s important. But now I know… thanks to you!

Greetings from Portugal.

Reply
SwagatamAdmin
November 20, 2022 • 4 years ago #135411

No problem Joao! thanks for sharing your kind feedback!

Reply
Constantinos
November 20, 2022 • 4 years ago #135495

Hello again Swagatam
Hello again João Sousa.
Since you want to build a power supply, it would be good to tell us what the use of the power supply will be, and what you will power.
In DC power supplies we don’t need the power, neither in VA nor in watts.
The important thing we need to know is, what is the maximum voltage we want at the output of the power supply, and what is the maximum current we want at the output.
In order to have a correct power supply, we calculate the voltage separately, and the amperes separately.
When we are going to power electronic devices, the current, but mainly the voltage is strictly necessary.
In power supplies, volts have the main reason. If the voltage is too less, the electronic device will not work, while if the volts are more the electronic device will burn.
If you want a general bench power supply, for experiments and tests, it would be good to choose a variable voltage power supply. A bench power supply, (+30) – 0 – (-30) up to 1.5 amps, is sufficient for testings.
If you want a power supply for something very specific, tell us what you want to power so we can guide you precisely.

Note: The translation is also done in the Portuguese language for a better understanding of the concept
=================================================
Olá novamente João Sousa.
Como você deseja fazer uma fonte de alimentação, seria bom nos dizer para que você a usará.
Em fontes de alimentação DC não precisamos de VA ou watts.
O importante que precisamos saber é qual é a tensão máxima que queremos que a fonte de alimentação nos dê na saída e qual é a corrente máxima que queremos na saída.
Para ter uma fonte de alimentação correta, calculamos a tensão separadamente e os amperes separadamente.
Quando vamos alimentar dispositivos eletrônicos, a corrente, mas principalmente a tensão, é estritamente necessária.
Em fontes de alimentação, os volts têm o principal motivo.
Se a tensão for muito menor, o dispositivo eletrônico não funcionará, enquanto se os volts forem maiores, o dispositivo eletrônico queimará.
Se você deseja uma fonte de alimentação de bancada geral, para experimentos e testes, seria bom escolher uma fonte de alimentação de tensão variável. Uma fonte de alimentação de bancada, (+30) – 0 – (-30) até 1,5 amperes, é suficiente para o testes.
Se você deseja uma fonte de alimentação para algo mais específico, diga-nos o que deseja alimentar para que possamos orientá-lo com precisão.

Reply
SwagatamAdmin
November 21, 2022 • 4 years ago #135574

Thank you Constantinos, for sharing this valuable information.

Reply
João Sousa
December 10, 2022 • 4 years ago #137131

Hi Swagatam and Constantinos, thank you for both replies.

Now I’m finishing my new training, and then I’ll decide the important parameters in the power supply I intend to build, as I was alerted here, for the various types according to their purpose.
I intend to build the power supply according to its specific purpose, as a final project of the basic training in Electronics that I started now.

Constantinos, you don’t need to worry about the translation into Portuguese either, your English / “Google English” is quite sufficient, your message has arrived without any problem. It’s just that I hate “Google’s Portuguese” translations; they don’t respect European Portuguese! … and I end up having to make an extra effort to understand.

Reply
SwagatamAdmin
December 10, 2022 • 4 years ago #137152

You are welcome Joao! All the best to you.

Reply
Constantinos
December 14, 2022 • 4 years ago #137422

Hello Swagatam
Hello João Sousa
I happen to know how to write the Spanish language, (I don’t know the pronunciation), so I know that translation is difficult when it comes to giving definitions of great importance with technical jargon, and the meaning of the words is not rendered correctly.
For example, if you ask me to explain the difference between electrical energy and electrical force, I won’t be able to help you because there are no corresponding words in English, nor in Portuguese, nor in Spanish that correctly convey the concepts.
This is why I can’t explain volt-amperes to you clearly.
Also, another difficulty is that, I don’t know the terminology of technology in Portuguese and English language.
Good morning from Greece.

Reply
SwagatamAdmin
December 14, 2022 • 4 years ago #137431

Hello Constantinos, I agree with you, translating and interpreting technical definitions from one language to another can be problematic, and unfortunately there’s no easy workaround to solve this issue.

Reply
Constanttinos
December 15, 2022 • 4 years ago #137441

Mr. Sagamatan, I don’t like to talk about myself, but now I am forced to do so, in order to raise the issue of translation.
Also, thank you for giving me the opportunity to explain some issues.
I teach through internet special course, in two schools outside Greece.
I have a lot of difficulty in translating when I have to convey the meaning of technical definitions.
The science of electricity includes a very large percentage of special way of thinking and words of philological type, and this makes the translation extremely difficult
Let me clarify that the concept of science is different from the concept of technology.
In a general context, science tries to interpret the fixed and unchanging laws of nature, while technology regulates the order in which the laws of nature are applied in conjunction with time, depending on the result we want to have.
“This”, how to explain it with scientific and technological terminology, and in another language?
Google translation is not to blame, because the problem starts with the words of the language that each person speaks, and the language helps the perception of the meaning.
I will give an example, although there are no correct words in English. Everyone talks about voltage and amperes, and to these two they give the meaning of power.
But, in the word “power” they do not give the meaning, but they give the unit of measurement.
The volt is the unit of measurement, not the force itself. Who is she is “this” force, and what is that a force?
In the Greek language, this force is called a tendency (Greek – “τάση” = trend in English). But the word trend has another meaning in the English language. So a correct translation cannot be made. But here I will speak with philological concepts and not with technological terminology.
When we have a material body (for example, a conductor) that has different electric charges at the ends of the body, then we say that the material body is in disequilibrium.
Another example: when a cloud has a different electric charge than the earth, then again we have an imbalance, but this imbalance is between two different materials.
The desire that the material body has to get out of imbalance, and to balance electrically, is called trend.
In simple words, the desire that a material body has to come to a state of equilibrium is called a trend.
In other words: the force that the body exerts on itself to balance is called trend, and we measure it in volts.
It’s desire, not voltage. Voltage is a measure of the body’s desire to balance itself electrically.
.
But I got tired, maybe some other time when I will have time and mood, I will continue, so that your readers will be better informed.
However, all that I mentioned is impossible to translate with technological terminology.

Reply
SwagatamAdmin
December 15, 2022 • 4 years ago #137453

Thank you for the explanation Constantinos! it is much appreciated. I hope the readers will find it useful.

Reply
arnold
September 24, 2023 • 3 years ago #145374

Dear Sir,
i’ve read to wonderful explaination concerning the VA of a transformer, I like to learn more about the computation and design of transformer.
will you please send me some, that I may learn and make my own transformer.
your consideration is highly appreciated, more power to you Sir.

Reply
SwagatamAdmin
September 24, 2023 • 3 years ago #145380

Thank you Arnold, Glad you found the post useful.
You can probably refer to the following post which explains a simpler method of calculating and configuring a transformer. Let me know if you have any further questions.

https://www.homemade-circuits.com/how-transformers-work/

Reply
Constantinos
November 19, 2022 • 4 years ago #135368

Mr. João Sousa, I have some time and I thought I would give some additional explanations, regarding the transformers, so that the rest of the readers can be enlightened.
When calculating a transformer, the first thing we need to know is how and where we will use the transformer.
Otherwise we calculate a power distribution network transformer, else we calculate a transformer to power an audio amplifier, else we calculate a transformer of an electrical device, else we calculate a transformer for amplitude modulation of transmitters.
But to help you understand some differences, I’ll break down the power distribution transformer, which brings 220 volts to our home.
These transformers are of high power, typically 1,500,000 VA
But be very careful. These transformers are made for 250 volt secondary winding, not 220 volt.
When we connect the load (consumer), then the 250 volts low of energy absorption from the consumer becomes 220 volts.
Now suppose that the secondary current of the transformer can deliver 1000 amperes. 1000 amperes times 250 volts is measured in VA because it is the apparent power. While 1000 amperes times 220 volts (which is the actual applied voltage) we measure it in watts.
This calculation is done when you apply AC directly to a consumer, and here the differences between VA and watts are large, and it makes sense to calculate them.
But when we have a household transformer that will feed an amplifier, the calculation changes, 1) because we will rectify the current, and 2) because the capacitors after the rectification, increase the voltage by about 12%.
That is, a transformer that has an alternating secondary winding voltage of 12Vac, and 1 ampere, when we rectify it, we will have 12 volts times 1.41 = 16.92 volts. Plus the 12% increase from the capacitors, the voltage will reach 19.22 volts. Here it makes no sense to calculate the difference between VA and watts, and we calculate the power directly in watts.
At this point, look at the difference. we have another power before the rectification (12 volts x 1 ampere = 12 watts AC), and another after the rectification 16.92 volts x 1 ampere = 16.92 watts DC). Whereas 19.22 volts times 1 ampere = 19.22 VA, because it is the apparent power, not the real one.
The transformer essentially converts the characteristics of the power, but does not convert the power itself, nor the frequency.
When we have a transformer with a primary winding of 220 volts 1 amp, the secondary can give us (example) 22 volts 10 amps.
That is, the power in both primary and secondary is the same. I don’t mention the transformer losses due to currents inside the core, which appear as heat, because they belong 96% to the secondary.
Actually the transformer transfers the consumed energy (power) of the load, from the secondary to the primary winding, and the primary transfers it to the generator.
I don’t have any more appropriate words than that, and unfortunately google translation doesn’t help with technical terminology.

Note: To clarify that, I am not electronic. I am an electrician technologist, and a radiation radio-electrician. I visit Swagatam website for electronics, because I don’t know electronics science, and I find the website reliable.

Reply
João Sousa
December 10, 2022 • 4 years ago #137128

Hello Swagatam and Constantinos, Thank you very much for your detailed explanation.
Now I understand the difference.

Best wishes,

João Sousa

Reply
Constantinos
November 17, 2022 • 4 years ago #135062

Hello Swagatam
I will translate two tables, and send them to you.
They are elements, for electrical machines for Power up to 1250 KW
Note: I used a translator. I don’t know the English language

Reply
SwagatamAdmin
November 18, 2022 • 4 years ago #135153

Thank you Constantinos, I appreciate your valuable feedback.

Reply
Rod Hepburn
December 29, 2022 • 4 years ago #138129

I need to make an audio transformer for an old telephone. One winding is 15 Ohms the other is 75 Ohms. Voltage supply is 3 volts.
An exisiting transformer is cylindrical and is 4 inches long by 3/4 inch in diameter with a laminated core.
Is it possible to specify wire diameter and number of turns in each coil.
Thankyou
Rod

Reply
SwagatamAdmin
December 29, 2022 • 4 years ago #138130

It can be difficult to suggest the number of turns, however the wire thickness on the 75 ohm side can be around 0.3mm and on the 15 ohm ohm this can be around 0.5mm
Since you have the resistance values for the respective winding, you can wind it by some trial and error until the specified resistance values are achieved.

Reply
John
January 4, 2023 • 4 years ago #138476

sir how many turns will be required for both primary and secondary sides of 0-6v 50amps center tap transformer

Reply
SwagatamAdmin
January 4, 2023 • 4 years ago #138501

John, the maximum current that can be used is upto 10 amps according to the above article…there’s no data given above this value in the relevant tables.

Reply
nitrous
January 9, 2023 • 4 years ago #138717

great tutorial! Thanks for sharing this. Have you done a tutorial on winding a 3 phase step up/down transformer? I’d like to use a VFD single phase to 3 phase inverter, but the output is 110vac. I need to step this down.
Any suggestions would be welcome!
Thanks
Doug

Reply
SwagatamAdmin
January 9, 2023 • 4 years ago #138722

Thank you!
I do not have a 3 phase transformer tutorial yet. If posible I will rty to investigate it.
For converting a 110V AC to lower levels only a step down transformer would work and can be used.

Reply
nitrous
January 9, 2023 • 4 years ago #138735

yes, the step down seemed to be the logical way to go – but doing with 1 transformer would certainly be easier than using 3, separate transformers 🙂
Thanks again for your comments and efforts.
Doug

Reply
Ali
March 7, 2023 • 3 years ago #140805

I have a transformer 50 kva 400/11000 v, if I doubled the low voltage turns, can I connect the low voltage side of the transformer to 800 volts source to step up to 11kv
Is there any issue will appear during operation

Reply
SwagatamAdmin
March 7, 2023 • 3 years ago #140812

Yes, as per the transformer standard formulas, that should be OK and possible.

Reply
Diltone
March 14, 2023 • 3 years ago #141001

Hi! I have been a fan of your work and i’m from the Philippines. I know it’s rude for me to ask but can you have sample calculation for a 750 watts transformer 50/60Hz that will be use in power inverter? I just want to have a sample and it serve as a guide as well. Hoping to hear your response soon! More power! \m/

Reply
SwagatamAdmin
March 14, 2023 • 3 years ago #141003

Thank you so much Diltone, I appreciate your kind words.
Yes I have a sample article which explains how to wind an inverter transformer, however the maximum current is only 10 amps. Here’s the link for the article:

https://www.homemade-circuits.com/how-to-design-your-own-inverter/

Reply
Diltone
March 14, 2023 • 3 years ago #141004

Thank you for the quick response! I just want to ask since I haven’t read the article and the link you sent me but I just want to know how much wattage that 10 amps will deliver?

Reply
SwagatamAdmin
March 14, 2023 • 3 years ago #141006

You can multiply 10 amps with the battery voltage, that will be the maximum wattage achievable from the transformer.

Reply
sreenivasulu dammu
June 9, 2023 • 3 years ago #143281

thank u sir , and can u pls share 16vdc to 14vdc 2n3055 transister based regulating power supply ckt diagram once.

Reply
SwagatamAdmin
June 9, 2023 • 3 years ago #143283

Try the second circuit from this article:

https://www.homemade-circuits.com/how-to-make-current-controlled-12-volt/

Reply
Vishwas B Rane
July 12, 2023 • 3 years ago #144058

Sir please meking the 1chapter choke design

Reply
James
July 31, 2023 • 3 years ago #144430

Great article but I’m still a little confused and don’t want to get it wrong. I’d like to build a transformer, 220v primary @ 60hz, 80v secondary with a max draw of 135 amps. Is that doable? I need help with core size and winding diameter. I’m assuming at 135amps it will get very hot if something is wrong.

Any input is appreciated,

Thank you

Reply
SwagatamAdmin
July 31, 2023 • 3 years ago #144436

I understand your requirement, but unfortunately the Tables in the above article support only upto 10 amp transformers, so 135 amp may not be possible using the above information

Reply
rajiv
September 28, 2023 • 3 years ago #145519

hello sir plz can you confirm that 1.152 is what and where you get this value.

Reply
SwagatamAdmin
September 28, 2023 • 3 years ago #145523

Hello Rajiv,
The 1.152 is a constant and is permanently included in the formula.

Reply
rajiv
January 24, 2024 • 3 years ago #148731

Thank you sir

Reply
Mubashir
September 29, 2023 • 3 years ago #145552

nice and usefull information

Reply
Julian
November 5, 2023 • 3 years ago #146697

Hi sir, thank you for the information. I would like to ask how you derive the equation of core area to get 1.152 x √(output voltage x output current) sq cm?

Reply
SwagatamAdmin
November 5, 2023 • 3 years ago #146700

Hi Julian, it is a standard formula, I do not have sufficient information regarding how the formula was derived.

Reply
Julian
November 5, 2023 • 3 years ago #146701

I see, appreciate for your help!

Reply
David Paul
December 7, 2023 • 3 years ago #147757

Hi.. Swagatam Thank you for the great works.

I think for high power designs we can either slightly decrease or increase the Bmax value or Power (watt) value to see the Cross sectional area, and then Check if it’s the same measurements with our real transformers Cross sectional area.

And with that we can knw if the transformer can deliver the actual power using the formula provided.

Reply
SwagatamAdmin
December 7, 2023 • 3 years ago #147760

Thanks David, you are correct, we can try that. Appreciate your feedback.

Reply
Moses
April 21, 2024 • 2 years ago #151655

No mention is made about the weight of the core itself. I thought the weight of the core in kg is an important factor in power handling of the transformer.

Reply
Jkbarik
January 3, 2025 • 2 years ago #167706

Hello. Swagatam
Hope you fine
Core area,= 1.152 sqrt (VA)
HOW this formula is derived?

Thanks

Reply
SwagatamAdmin
January 3, 2025 • 2 years ago #167708

Hi JK,
Output Voltage (V) is the voltage that comes out of the transformer’s secondary side.
Output Current (A) is the current that flows out of the transformer’s secondary side.
√(Output Voltage * Output Current) shows the apparent power (VA) of the transformer.

The number 1.152 is a constant and is derived by experimenting with the following factors of an iron core transformer::

Magnetic Flux Density (B): This is a common value for iron-core transformers usually between 1.2 and 1.5 Tesla.
Frequency (f): This refers to the usual mains frequency which is either 50 or 60 Hz.
Efficiency: Transformers don’t work at 100% efficiency in real life so this number helps to factor in losses from things like core saturation, hysteresis, and eddy currents.
Practical Design Adjustments: This includes industry standards and safety margins.

Reply
Jkbarik
January 4, 2025 • 2 years ago #167730

Hello Swagatam
Thanks for your reply.

Now inverter 24v to 230v. 900va

CA=35cm2
TPV=1.0
Primary turns=24nos. 40amp 8swg
Sec turns=. 230nos. 4amp. 18swg

Now which bobbin and crgo EI core should I choose for the best result?

Hope you best
Happy New year

Reply
SwagatamAdmin
January 5, 2025 • 2 years ago #167737

Hello JK,
I think only a transformer expert would be able to suggest you correctly about the exact dimensions.
Basically, Use a bobbin that matches the EI core size. For a 35cm^2 core area, the EI core size would likely be between EI 96 and EI 120.

Reply
Barclay Momin
December 21, 2025 • 7 months ago #196517

A Stranger CUBE 80 model amplispeaker mains transformer was burnt. Due to the burnt, the winding turns cannot be counted anymore. The bobbin area core is 1.2 x 1.2 sq inch (3.2 x 3.2 sq cm or 32mm x 32mm). The 220 volt primary secondary winding uses 32 SWG copper wire. Also the output secondary winding for 0 – 40 volt winding uses 32 SWG. The output of 9 – 0 – 9 volts uses 30 SWG. Another output of 25 – 0 – 25 volt uses 22 SWG. Please calculate for me the number of turns of winding of the (1) 220 volt primary, and (2) for the 40 volts. Thank you, Sir.

Reply
SwagatamAdmin
December 21, 2025 • 7 months ago #196534

Momin, I will try to solve it for you once I am free from my pending assignments, in the meantime you can also try calculating using the procedures given above…

Reply
Malcolm Robertson
April 6, 2026 • 4 months ago #204207

Hi
I followed a circuit instruction to wind a step up transformer 15 winds on the primary side 45 on the other. I used 0.6mm insulated hook up wire.
I connected the primary to a wall wart , a volt meter to the secondary and got nothing on the volt meter. the windings are on opposite sides of 20mm x 1.6 mm box section 12mm wide. Resistance test doesn’t indicate broken wires or contact with the box section former. Why doesn’t my transformer work?

Reply
SwagatamAdmin
April 6, 2026 • 4 months ago #204228

Hi, if you did everything correctly then your transformer should have started working immediately. There must some winding issue or lamination core issue which may be causing an error. You can read the following article for more info:
https://www.homemade-circuits.com/how-transformers-work/

Reply
« Back to Newest Comments

Need Help? Please Leave a Comment! We value your input—Kindly keep it relevant to the above topic! Cancel reply

Your email address will not be published. Required fields are marked *

Primary Sidebar



Categories

  • Arduino Projects (95)
  • Audio and Amplifier Projects (134)
  • Automation Projects (18)
  • Automobile Electronics (103)
  • Battery Charger Circuits (89)
  • Datasheets and Components (109)
  • Electronics Theory (150)
  • Energy from Magnets and Earth (40)
  • Games and Sports Projects (11)
  • Grid and 3-Phase (20)
  • Health related Projects (27)
  • Home Electrical Circuits (13)
  • Indicator Circuits (16)
  • Inverter Circuits (100)
  • Lamps and Lights (163)
  • Meters and Testers (72)
  • Mini Projects (28)
  • Motor Controller (68)
  • Oscillator Circuits (30)
  • Pets and Pests (15)
  • Power Supply Circuits (91)
  • Remote Control Circuits (50)
  • Security and Alarm (65)
  • Sensors and Detectors (107)
  • SMPS and Converters (46)
  • Solar Controller Circuits (62)
  • Temperature Controllers (44)
  • Timer and Delay Relay (50)
  • Voltage Control and Protection (44)
  • Water Controller (37)
  • Wireless Circuits (31)



Circuit Simulator

circuit simulator image



Subscribe to get New Circuits in your Email



Other Links

  • Privacy Policy
  • Cookie Policy
  • Disclaimer
  • Copyright
  • Videos
  • Sitemap

People also Search

555 Circuits | 741 Circuits | LM324 Circuits | LM338 Circuits | 4017 Circuits | Ultrasonic Projects | SMPS Projects | Christmas Projects | MOSFETs | Radio Circuits | Laser Circuits | PIR Projects |



Recent Comments

  • Swagatam on 2 Cool 50 Watt Inverter Circuits for Students and Hobbyists
  • Swagatam on The Perfect FM Radio Circuit using TDA7000 IC
  • Swagatam on 9 Simple Sine Wave Generator Circuits Explored
  • way on 2 Cool 50 Watt Inverter Circuits for Students and Hobbyists
  • Athull on The Perfect FM Radio Circuit using TDA7000 IC

Social Profiles

  • Twitter
  • YouTube
  • Instagram
  • Pinterest
  • My Facebook-Page
  • Stack Exchange
  • Linkedin

© 2026 · Swagatam Innovations